Jlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined Transformer

Application: Electronic, Instrument
Type: Combined Transformer
Phase: Three
Operation Condition: Outdoor
Usage: Protection, Measurement
Winding Form: Single Layer & Tightly Wound Type

Products Details

  • Overview
  • Product Description
  • Product Parameters
  • Detailed Photos
Overview

Basic Info.

Model NO.
JLSZV2-6
Insulating Medium
Epoxy Resin
Installation
Strut Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Transport Package
Wooden
Trademark
KODERY
Origin
China
HS Code
850431
Production Capacity
10000PCS/Month

Product Description







 
Product Description

JLSZV2-6,10W COMBINED TRANSFORMERS
TECHNICAL DATA
The products accord with the standards of GB17201-2006 and some special demands
Rated frequency 50HZ/60HZ
Ambient temperature -15ºC - +55ºC
Altitude not more than 4500M


This type of voltage transformer adopts epoxy-resin vacuum casting, assembled by 4 single phase winding is applicable for power systems of rated frequency 50Hz or 60Hz and rated voltage up to and including 10kV, used for electric energy metering and voltage measurement. It is featured with long creepage distance, high secondary output capacity, stable insulation, excellent performances against pollution, UV or acid rain,etc. Special specifications with load control output and power output are available at request.
It complies with the standards GB 20840.1-2010 Instrument transformers-Part 1: General requirements, GB 20840.2-2014 Instrument transformers-Part2:Additional requirements for current transformers, GB20840.3-2013 Instrument transformers-Part3:Additional requirements for inductive voltage transformers and GB 20840.4-2015  Instrument transformers-Part 4: Additional requirements for combined transformers.
Jlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined Transformer

Product Parameters
Type Rated voltage ratio(V) Accuracy class and rated secondary output(VA) Limit output(VA) Rated insulation level(KV)
JLSZV2-6W 6000/100 0.2-2×20
0.5-2×50
1-2×80
3-2×200
2×400 7.2/32/60
JLSZV2-10W
10000/100
12/42/60
Rated primary current(A) Single transformation ratio Accuracy class and rated secondary output(VA) 1s thermal current(KA) Rated dynamic currnet(KA)
(0.2)s 0.5s 0.5
7.5-10-15 7.5

10


 


10


 


15


 
1.0 2.5
10-15-20 10 1.5 3.75
15-20-30 15 2.4 6.0
20-30-40 20,25 3.0 7.5
30-40-50 30 4.5 11
40-50-75 40 8 20
50-75-100 50 9 22.5
75-100-150 75 12 30
100-150-200 100 16 40
 
Rated primary current(A) Single transformation ratio Accuracy class and rated secondary output(VA) 1s thermal current(KA) Rated dynamic currnet(KA)
(0.2)s 0.5s 0.5
150-200-300 150 10 10 15 24 60
200-300-400 200,250 32 80
300-400-500 300 45
400-500-600 400 60 100
Jlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined TransformerJlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined TransformerJlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined Transformer
Detailed Photos

Jlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined TransformerJlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined Transformer

Jlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined Transformer

Jlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined TransformerJlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined TransformerJlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined TransformerJlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined TransformerJlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined TransformerJlszv2 -10 (6) W Outdoor / Three-Phase Epoxy-Resin Type Combined Transformer

 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours